零件编号 | 融合 | 尺寸 | 平均值@250KA/1500Vdc | 功率损耗(W)1.0In | ||
安培 | A²s 熔化 | A²s 清算 | ||||
恒顺恒通VT1500400-105S-XNUMXE | 400 | 4# | 25,834 | 136,415 | 190 | |
恒顺恒通VT1500500-105S-XNUMXE | 500 | 4# | 57,389 | 276,828 | 195 | |
恒顺恒通VT1500630-105S-XNUMXE | 630 | 4# | 117,654 | 567,527 | 228 | |
恒顺恒通VT1500700-105S-XNUMXE | 700 | 4# | 162,326 | 783,014 | 245 | |
恒顺恒通VT1500800-105S-XNUMXE | 800 | 4# | 240,110 | 1,158,220 | 255 | |
恒顺恒通VT1500900-105S-XNUMXE | 900 | 4# | 345,759 | 1,667,836 | 276 | |
恒顺恒通VT15001000-105S-XNUMXE | 1000 | 4# | 470,616 | 2,270,110 | 290 | |
恒顺恒通VT15001100-105S-XNUMXE | 1100 | 4# | 623,250 | 3,006,366 | 310 | |
恒顺恒通VT15001200-105S-XNUMXE | 1200 | 4# | 754,483 | 3,620,561 | 319 | |
恒顺恒通VT15001250-105S-XNUMXE | 1250 | 4# | 918,230 | 4,429,260 | 326 | |
恒顺恒通VT15001300-105S-XNUMXE | 1300 | 4# | 1,009,830 | 5,254,527 | 335 | |
恒顺恒通VT15001350-105S-XNUMXE | 1350 | 4# | 1,294,848 | 6,245,949 | 347 | |
恒顺恒通VT15001400-105S-XNUMXE | 1400 | 4# | 1,399,970 | 6,986,564 | 352 | |
恒顺恒通VT15001500-105S-XNUMXE | 1500 | 4# | 1,581,795 | 7,630,093 | 360 | |
恒顺恒通VT15001600-105S-XNUMXE | 1600 | 4# | 1,927,554 | 9,297,929 | 372 | |
恒顺恒通VT15001800-105S-XNUMXE | 1800 | 4# | 2,734,600 | 13,190,870 | 392 | |
*HCHVT15002000-105S-XNUMXE | * 2000 | 4# | 3,603,985 | 18,860,380 | 410 | |
*:如有要求请先与原厂工作人员沟通。 |