产品描述
HCSPD1 串联电涌保护器属于 T2 光伏系统的直流侧避雷器。 当系统因雷击或其他原因出现过电压时,保护器立即在纳秒级开启,将过电压引入大地进行放电,从而保护电网上的设备。
它们具有可靠的电压保护水平、超级浪涌放电能力和安全过载能力,用于光伏发电系统的雷电保护。
该产品配备了高能动芯片,当系统因雷击或其他原因出现过电压时,能以纳秒级的响应速度将电压引入大地,从而保护设备。
技术规格
Parameter | Model 600 | Model 1000 | Model 1500 |
---|---|---|---|
Structure | U - Type | Y - Type | Y - Type |
Maximum Continuous Operating Voltage (Ucpv) | 600V | 1000V | 1500V |
Nominal Discharge Current (PV In) | 20kA | 20kA | 20kA |
Maximum Discharge Current (Imax) | 40kA | 40kA | 40kA |
Voltage Protection Level (Up) | 3.0kV | 3.0kV | 3.0kV |
Response Time (T) | ≤ 25ns | ≤ 25ns | ≤ 25ns |
Degrees of Protection Provided by Enclosure | IP20 | IP20 | IP20 |
Remote Signaling Contact (Optional) | 11, 14 normally open; 11, 12 normally closed | 11, 14 normally open; 11, 12 normally closed | 11, 14 normally open; 11, 12 normally closed |
Local Alarm Indication | Normal green, fault red | Normal green, fault red | Normal green, fault red |
Installation Method | 35mm mounting rail | 35mm mounting rail | 35mm mounting rail |
机械与环境
Parameter | Specification | |
---|---|---|
Operating Temperature Range | Ta | -40 ºF to +158 ºF [-40 ºC to +70 ºC] |
Permissible Operating Humidity | RH | 5%...95% |
Atmospheric Pressure and Altitude | 80 kPa ... 106 kPa / -500 m ... 2000 m | |
Terminal Screw Torque | Mmax | 39.9 lbf·in [4.5 Nm] |
Conductor Cross Section (max) | 2 AWG (Solid, Stranded)/ 4 AWG (Flexible)<br>35 mm² (Solid, Stranded)/ 25 mm² (Flexible) | |
Mounting | 35 mm DIN Rail, EN 60715 | |
Degree of Protection | IP 20 (built-in) | |
Housing Material | Thermoplastic: Extinguishing Degree UL 94 V-0 | |
Thermal Protection | Yes | |
Operating State / Fault Indication | Green ok / Red defect | |
Remote Contacts (RC) Option | Yes | |
RC Switching Capacity | AC: 250V / 0.5 A; DC: 250V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A | |
RC Conductor Cross Section (max) | 16 AWG (Solid)/ 1.5 mm² (Solid) |
产品模型
HC | D | ǞǞǞ | 1 – | □ | □ – | □ | □ | |||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
公司代码:HC= 和成电气 |
||||||||||||
D=DC | ||||||||||||
产品代码:P=浪涌保护器 | ||||||||||||
系列 | ||||||||||||
电压代码:T= 1500VDC | ||||||||||||
Imax: 40=40 KA | ||||||||||||
极点形式代码:3= 3P | ||||||||||||
遥控信号:R=有RC N=无RC |